返回技能市场

楼宇设备自动化运维

Building edition of iaiops — facility / HVAC / BMS / 厂务 over BACnet/IP (ASHRAE 135): Who-Is discovery, object/point lists, presentValue snapshots, COV capture, TrendLog reads, one MOC-gated property write; plus Modbus-TCP/RTU for meters/chillers and optional plain MQTT for IoT sensors, with the cross-protocol brain. Use when the task mentions BACnet, BACnet-IP, HVAC, AHU, chiller, VAV, BMS, building automation, facility management, 厂务, 楼宇自控, Who-Is, presentValue, or TrendLog; also IO-Link masters for smart building sensors (JSON interface, read-only), and the vendor supervisory-controller REST layer above BACnet (Metasys/OpenBlue, Niagara/oBIX) for point/alarm/trend reads and one MOC-gated command. Read-first, MOC-gated writes.

版本: 1.0.1分类: 办公效率
中文

SKILL.md

iaiops-building — 楼宇/厂务 edition(BACnet + Modbus + IO-Link + MQTT + 脑)

启动:IAIOPS_MCP=building / iaiops-mcp-building(= bacnet + modbus + opcua + iolink + 脑)。 IoT 传感器走 MQTT 时叠加:IAIOPS_MCP=building,sparkplug。 安装:pip install iaiops[building]。BACnet 的 host 是本机 BACnet/IP 接口 (ip 或 ip/mask)。

工具

BACnet/IP(read-first;暖通/楼宇/厂务)

  • bacnet_discover — Who-Is:本地 BACnet/IP 网上的设备
  • bacnet_object_list — 设备的 object/point 列表
  • bacnet_read_property — 单对象属性(默认 presentValue)
  • bacnet_read_points — 所有 analog/binary/multistate 点的 presentValue(HVAC 快照)
  • bacnet_cov_subscribe — 单对象有界 Change-of-Value 捕获
  • bacnet_read_trend_log — 读设备 TrendLog 缓冲记录
  • bacnet_write_property — [WRITE][HIGH][MOC] 写单对象属性(默认 off: dry_run=True + 审批双确认;可指挥楼宇设备 — 设定值、输出)

Modbus-TCP / Modbus-RTU(只读;电表/冷机/表计)

  • modbus_read_holding modbus_read_input modbus_read_coils modbus_read_discrete
  • modbus_detect_byte_order / modbus_list_templates / modbus_apply_template
  • modbus_health_summary

IO-Link(只读;主站 JSON 接口 — 楼宇智能传感器)

  • iolink_master_info — 主站身份(/deviceinfo)
  • iolink_ports — 有界端口扫描(≤32:mode/status + 在线设备身份)
  • iolink_device_info — 单端口设备身份
  • iolink_read_pdin — 过程数据输入(raw hex + 字节数组;按 IODD 解码)
  • iolink_read_isdu — ISDU 参数读(index/subindex 有界)
  • iolink_scan — 主站 + 全端口一次性快照
  • 配置 flavor: iotcore(ifm IoT-Core,默认)或 rest(plain-REST 主站);v1 只读

BAS 控制器层(edition 工具;厂商监控控制器 REST,在 BACnet 之上)

厂商监控控制器(Johnson Controls Metasys/OpenBlue、Tridium Niagara oBIX/REST)把大量 BACnet 现场点/告警/趋势聚合在一个带鉴权的企业 REST 接口后面——与 bacnet(现场总线)互补、非重复。 Bearer/token 从加密 secret store 按 key 取(secret_name),不走明文参数。

  • bas_point_list — 列控制器 point/object(跨厂商归一化:id/name/value/unit/status)
  • bas_point_read — 单/多点 present-value
  • bas_alarm_list — 控制器活动告警/事件(归一化)
  • bas_trend_read — 单点历史趋势样本(有界 ≤5000)
  • bas_command — [WRITE][HIGH][MOC](默认 off:dry_run=True + 审批双确认;捕获改前值供 undo)。 生命安全点(fire/smoke/egress/加压)一律拒绝——联网前即拒,绝不下发。
  • 厂商方言(metasys/niagara:资源路径 + 字段别名)仅存在于连接器内;oBIX 原生 XML / 精确写语义 待核实。

MQTT(可选叠加 sparkplug 组;IoT 传感器/网关)

  • mqtt_read_topic — 裸 MQTT 有界收集;uns_browse — 主题树浏览
  • 完整 Sparkplug B/UNS 工具清单见 iaiops-factory skill
  • mqtt_publish — [WRITE][HIGH][MOC](默认 off)

楼宇专属(edition 工具;仅随 building edition 加载,不进全局脑)

  • economizer_check — AHU 经济器故障检测(FDD):检出同时供冷供热(纯浪费)、该用自然冷却 却没用(室外够冷但新风阀在最小位且机械制冷开)、越高限还开阀(把热风引进来)。逐 AHU 判定, worst-first,每故障引用温度/状态。读数来自 BACnet AI/BI 点。
  • zone_comfort — 区域舒适度 + 室内空气质量(ASHRAE 55/62.1):逐区判温度 20–26°C、相对湿度 30–60%、CO₂ ≤1000 ppm(通风充分性代理),越界即 breach,worst-first,引用数值。读数来自 BACnet AI 点。

跨协议脑(永远随 server 暴露)

  • 诊断:diagnose_dataflow downtime_root_cause downtime_root_cause_live downtime_triage learn_cause_weights rca_corpus_from_maintenance historian_health alarm_bad_actors tag_health subscription_health heartbeat_health alarm_flood_analysis alarm_cascade alarm_rationalization_worksheet
  • 告警事件聚类:alarm_event_clusters — alarm_bad_actors 按来源排名,回答的是「哪台仪表最吵」, 不是「哪个故障最吵」;一个把同一条件写成十种说法的厂会得到十个 bad actor。这个按事件说了什么分组。 合并规则是去掉大小写/标点/数字后的精确相等,不是相似度 —— 故意做笨,所以不需要模型、且可核对; 每个簇都列出被合并的原文与来源。它不主张两条措辞不同的告警是同一个故障,那由人判断。
  • 数据质量:data_quality_scorecard data_quality_fleet_rollup
  • 分析:oee_compute downtime_events oee_multidim monitor_changes health_summary (deprecated) anomaly_scan (deprecated)
  • 上下文基线:baseline_learn_contextual baseline_check_in_context —— 一个位号只学一条带, 在它有不止一个「正常」时就是错的(同一台干燥机 recipe A 走 180 °C、B 走 240 °C,一条带横跨两者, 于是两个工况都不可能出错)。上下文由人声明,绝不推断(D16);某个上下文历史太薄就拒学, 不借用别的上下文的样本;读数落在没学过的上下文里报 unknown_context,绝不回落到全局带 —— 回落等于把「这个工况从没见过」说成「这个工况正常」。
  • 上下游归因:downtime_attribution —— RCA 只按时间加权,所以一次上游停机会让每台下游设备 各自给出一个自信的本地根因。方向来自声明的产线顺序(D25:产线上共现是必然,拿它挖边等于 制造因果),顺序来自时间戳,两者都要成立;没声明关系就报 not_evaluable 并给出补法。
  • 资产:asset_inventory cross_protocol_asset_model adopt_alias_map diff_alias_map
  • 设备公告对照:device_advisory_check —— scan 早就在读 vendor/model/firmware,却什么都没做。 这条把它接上,并刻意停在漏洞扫描器会继续往前走的地方:只报「落在公告声明的版本范围内」, 不说「可利用」、不给严重度 —— 可达性与补偿控制决定那件事,而只读扫描看不见它们。 不内置任何 CVE 库(过期却看着像最新的库比没有更糟),由现场挂载文件、离线可用,每条必须带来源。 读不出固件报 version_unknown,读得出但排不了序报 version_unparsed —— 都不算通过; 公告没提到的设备不出现在结果里,那是「未知」不是「没有」。
  • 基线:baseline_learn baseline_check baseline_record_change baseline_status (change-log 基线:拒学薄历史、只报持续越带、每次告警必引基线样本 —— 非黑盒异常检测)
  • 合规/信创:compliance_mapping compliance_frameworks compliance_dengbao_levels compliance_report compliance_evidence_bundle historian_push export_data historian_query historian_coverage stream_publish uns_publish stream_publish_event rca_narrate fleet_status fleet_incidents pdm_forecast historian_push export_data
  • 程序解读:plc_program_outline plc_program_xref plc_program_section plc_program_visibility(解读导出的 ST/AWL/L5X 程序,只读文件,强制引用行号)
  • 程序变更基线:plc_program_snapshot plc_program_drift plc_program_history — 把「认可的那一版」 的结构记下来(文件 SHA-256 + 每个 block 的结构指纹:声明/调用/分支条件/定时器,不含行号、注释、 block 顺序,所以在文件顶上加一行注释不会把整份程序报成变更),之后问某一次导出动没动。 三个判词咬得很紧:identical 只由 SHA-256 相同得出;logic_changed 逐 block 指出哪一类变了; changed_outside_extracted_structure = 字节变了而结构指纹全同 —— 多半是注释/排版,但这些 parser 是结构抽取不是文法,所以它不叫「仅文档」,也不构成放行。删历史只在 CLI(iaiops program forget): 删变更控制证据不该离 agent 只有一次调用。存的是 block 名 + 哈希 + 计数,不落声明、源码行和注释。
  • 医疗设施(healthcare facility 安全):isolation_room_check — 隔离病房压差合规(ASHRAE 170 / CDC:空气传染隔离 AII 负压、保护性环境 PE 正压,≥2.5 Pa);检出反向/不足/低裕度,worst-first,每项引用读数。读数来自 bacnet_read_points 的压差 AI 点或历史库,纯分析。
  • 自证:verify_determinism — 把「拿掉模型、断网、同一份数据重跑、输出逐字节相同」跑出来: 固定数据集过一遍分析层,规范化后取 SHA-256,在本进程跑两遍、再在两个不同 PYTHONHASHSEED 的 全新解释器里各跑一遍(这一臂才抓得到集合/字典迭代顺序渗进结果),全程 socket 抛异常。 给 CSV/验证团队的是一条能写进 IQ/OQ 的测试用例,不是一句形容词。
  • 元:protocols_supported(产品能做什么)· site_readiness(这个站点今天能跑什么、还差什么;零联网) · onboarding_status(先判定路线:设备直读 / 已在 UNS broker,UNS 再按已存体检分 B1/B2;再给这条路上的下一步;零联网) · onboarding_config_draft(把已存的 scan 变成 config.yaml 端点草稿 —— 只写连接事实: value: null 的字段是扫描没确认的,照抄它的 caution,别替人填也别删;tags 永远是空的, 点位语义只能人来确认 iaiops tags export|apply)
  • 调查层(§13,八步证据闭环):investigation_readiness investigation_open investigation_show investigation_list — 「真出事时这个站能走到第几步、每个缺口还差什么」,以及对一个已过去的窗口 逐步走完并留档(不碰设备)。缺口分两种:你没供(给命令) 与 产品供不了。
  • 产线关系与机制库:line_relation_declare line_relations_list mechanism_library_check mechanism_library_list — 上下游由人声明(D25:线上下游共现是必然,推不出因果); 机制库按 ISO 14224 分 mode/mechanism/cause,可排除、绝不确认, 库里没有这条原因 → nothing_known(不是「无异议」)。

Workflows

  1. Doctor-first:protocols_supported → iaiops doctor → bacnet_discover (Who-Is 有响应才谈读点)。
  2. Read-first:bacnet_object_list → bacnet_read_points 快照 → 趋势用 bacnet_read_trend_log,变化捕获用 bacnet_cov_subscribe; "没数据"用 diagnose_dataflow,坏点排名用 tag_health。
  3. MOC 写:bacnet_write_property(与可选 mqtt_publish)为 [WRITE][HIGH][MOC]:默认 dry_run=True、捕获改前值供 undo、 iaiops approve 具名审批双确认。写设定值可影响在运楼宇设备 —— 未经授权绝不写。

支持版本矩阵(内部 HLD §8,设计文档不随本仓发布;待核实 不得当既成事实)

协议库(pin)规范/版本覆盖传输自测
BACnet/IPBAC0>=2023.6,<2026(extra)ASHRAE 135 Annex J暖通/楼宇/厂务控制器UDP/47808✅ 读路径 verified 2026-07-02(真 bacpypes3 虚拟设备);live HVAC 写/COV/trend 待核实
Modbus-TCPpymodbus>=3.5,<4App 1.1b3;FC 1/2/3/4/5/6/15/16电表/冷机/任意 TCP 从站TCP/502✅
Modbus-RTUpymodbus>=3.5,<4 + pyserial>=3.5Modbus serial (RTU)串口表计RS-485/serial✅ socat PTY verified 2026-07-02;物理 RS-485 待核实
IO-Linkrequests>=2.31,<3(复用 MTConnect pin)IO-Link Master JSON Integration(IOLINK-JSON);ifm IoT-Core / plain-REST 双 flavor带 JSON/REST 接口的主站(ifm/Balluff/Turck 类)HTTP REST/JSON✅ mock 主站(双 flavor);live master 待核实
MQTTpaho-mqtt>=2.0,<3MQTT 3.1.1/5(裸 MQTT + SpB)IoT 传感器/网关/BrokerTCP/1883/8883✅
BAS: Metasys OpenBlue RESTrequests>=2.31,<3(复用 MTConnect pin,无新 HTTP 依赖)Metasys REST API v4(/objects·/alarms·/trendedAttributes);JC OpenBlue 监控控制器NAE/SNE/SNC 类监控控制器聚合的 BACnet 现场点HTTPS + Bearer token✅ mock 控制器(in-repo);live 设备写/trend/告警 待核实
BAS: Niagara 4 oBIX/RESTrequests>=2.31,<3(复用 MTConnect pin,无新 HTTP 依赖)Niagara 4 oBIX/REST(/obix/config·/obix/alarms·/obix/histories);JSON 建模,原生 oBIX-XML 待核实Tridium JACE / Niagara Supervisor 下的点/告警/历史HTTPS + Bearer token✅ mock 控制器(in-repo);live 设备 + oBIX-XML 编码 待核实

评论与讨论

0/2000

还没有评论,分享你的体验吧。